|
To CD Home >
Drinking Water >
To In House Compliance>
Sampling Requirements
Ground Water Rule
Florida's public water systems (PWSs) that use ground water will
have to comply with the Ground Water Rule (GWR) beginning December
1, 2009. The Ground Water Rule (GWR) was adopted and incorporated by
reference into Rule 62-550.828, F.A.C., effective December 30, 2011.
The GWR applies to all PWSs that use ground water except for those that
combine all of their ground water with surface water, including ground
water under the direct influence of surface water, prior to treatment of
the surface water. For the purposes of the GWR, "ground water system" (GWS)
means any PWS meeting the above criteria, including consecutive systems
receiving ground water from a wholesale system.
The primary goal of the GWR is to provide increased protection against
microbial pathogens, specifically bacterial and viral pathogens.
The basic requirements of the GWR include the following:
-
Sanitary surveys,
-
Ground water source microbial monitoring,
-
Treatment technique requirements, and
-
Public notification.
Sanitary surveys are primarily the responsibility of the FDEP, while
GWSs are responsible for the other three requirements.
Triggered source water monitoring is used to determine if fecal
contamination is present in a ground water source/well. A GWS must
conduct triggered source water monitoring if:
When conducting triggered source water monitoring:
-
The GWS must collect at least one source
water sample for each day one or more TC+ routine distribution
system samples were collected by a GWS from each well pumped on
the day of the TC+ sample(s) was (were) collected.
-
These
"initial" triggered source water samples must be collected
within 24 hours of notification of the TC+ routine distribution
system sample (s) at a location prior to any treatment
-
The samples must be analyzed for one of the following three fecal
indicators: E. coli, enterococci, or coliphage.
If an "initial" triggered source water sample is
fecal-indicator-positive (FI+):
-
The GWS must collect five additional source water samples from the
same source/well within 24 hours of being notified of the FI+
sample.
-
These
"additional" triggered source water samples must be analyzed
for one of the three fecal indicators above. (The "additional"
samples may be analyzed for a different fecal indicator than that
used for the "initial" sample.)
-
If
any one of the five "additional" triggered source water samples is FI+, the GWS must implement
corrective action.
Consecutive GWS that has a TC+ routine distribution system sample:
-
Must notify its wholesale GWS(s) within 24 hours of being notified
of the TC+ sample.
-
The wholesale GWS(s) must conduct, within 24 hours of being notified
by the consecutive GWS, triggered source water monitoring unless the
wholesale GWS provides FDEP-approved four-log virus treatment for
each ground water source/well serving the consecutive GWS.
Assessment source water monitoring is source water monitoring
that is in addition to triggered source water monitoring and that also
is used to determine if fecal contamination is present in a ground water
source/well. For the purposes of the GWR, the raw water monitoring
currently required in Rule 62-550.518, F.A.C., is considered assessment
source water monitoring.
If a raw/assessment source water sample is FI+:
-
The GWS may, instead of immediately implementing corrective action,
take five "additional" raw/assessment source water samples from the
same source/well within 24 hours of being notified of the FI+
sample.
-
If any one of the five
"additional" raw/assessment source water
samples is FI+, the GWS shall implement
corrective action in accordance with Rule
62-555.315(6)(f), F.A.C., and the GWR.
A
GWS may use a triggered source water sample to meet the assessment
source water monitoring requirements in Rule 62-550.518, F.A.C. Also, a
GWS may use an assessment source water sample collected under Rule
62-550.518, F.A.C., to meet triggered source water monitoring
requirements if the assessment source water sample was collected on the
same day the TC+ routine distribution system was collected or on any day
thereafter up until 24 hours after notification of the TC+ sample.
Ways to Reduce the Burden of Triggered or Assessment Source Water
Monitoring [.doc 30 kb]
Corrective action is required when:
-
An
"additional" triggered or assessment source water sample is FI+ or,
-
A significant deficiency is identified by the FDEP during an
inspection. Significant deficiencies include defects in design,
operation, or maintenance and include a source, treatment, storage, or
distribution facility failure or malfunction that could cause
contamination of water.
GWSs must consult with the FDEP regarding the appropriate corrective
action within 30 days of receiving written notice from the FDEP of a
significant deficiency or written notice from a laboratory that an
additional triggered or assessment source water sample was found to be
FI+. Within 120 days of receiving such a written notice, GWSs must
either have completed corrective action or be in compliance with an FDEP-approved
corrective action plan and schedule. Also, if the FDEP specifies any
interim measures for protection of public health pending completion of
corrective action, GWSs must comply with those interim measures.
Corrective action alternatives include the following:
-
Correct all significant deficiencies.
-
Provide an alternate source of water.
-
Eliminate the source of contamination.
-
Provide 4-log virus treatment before or at the first customer
for the ground water source.
Compliance monitoring:
-
Must be conducted by GWSs that either provide four-log virus
treatment as a corrective action or provide four-log virus treatment
instead of conducting triggered source water monitoring.
-
GWSs using chemical disinfection to achieve four-log virus
treatment and serving more than 3,300 people must continuously monitor
the residual disinfectant concentration at the end of the disinfectant
contact zone, which must be before or at the first customer.
Additionally, pH and temperature must be checked daily at or before the
first customer during the period of peak flow.
-
GWSs using chemical disinfection to achieve four-log virus
treatment and serving 3,300 or fewer people must take a daily grab
sample at the end of the disinfectant contact zone during peak flow.
Additionally, pH and temperature must be checked daily at or before the
first customer during the period of peak flow.
The following table outlines the various situations or violations for
which notification
is required and the corresponding types of notification that are
required.
Central District
Drinking Water Section
3319 Maguire Blvd.,
Suite 232
Orlando, Florida
32803-3767
Compliance Fax:
407-897-4189
If you have technical problems with the functioning of this web site,
please e-mail
our webmaster.
|